Back

Isolators / Converters
 

Type

H641

H6570 H6580 H6410 H6400

Input

0/4...20mA, 20...4mA, 0...5/10V, 10...0V, -10...+10V, 2-wire 4...20mA, potentiometer, mV-input

4...20mA loop powered isolator but also converter 4...20mA, 0...10V max. 5kHz, min. 0...5V, max. 0...24V, Namur, NPN-/PNP-sensor, closing contact, pick-up max. 5kHz, min. 0...5V, max. 0...24V, Namur, NPN-/PNP-sensor, closing contact

Output

0/4...20mA, 20...4/0mA reversed, 0...5/10V, 10...0V reversed, -10...+10V, 2-wire 4...20mA passive output

0...20mA, 4...20mA, 0...10V, loop powered converter 4...20mA 2-wire connection 0/4...20mA 0/4...20mA selectable pulse divider 1...4096 via DIP-switches closing or opening contact

Selection

DIP-switches & jumpers

Factory selected Factory selected By DIP-switches Range resistors

Galvanic isolation

1,000V

2,000V Optical, 1,000 VDC

Power supply

22...30 VDC

Loop powered 2-wire transmitter, 12...36 VDC 22...30 VDC 230, 115 VAC, 24 VDC/AC

Effect demand

40 mA V-output, 60 mA I-mA output, 80 mA 2-wire output

Input voltage drop example below   60 mA 2 VA

Accuracy

< 0.05 % of span

< 0.05 % of span 0.05 % of span 0.3 % of span 0.2 % of span

Typical linearity

< 0.05 % of span

< 0.03 % of span 0.05 % of span

Input resistance

50 W for current, > 100 MW for voltage

50 W for current

Output load

max. 500 W

max. 300 W 2-wire output max. 500 W 500 W

Response time

Selectable damping 10, 250, 500, 700 ms

100 ms 100 ms 3 s (output 63 %) 1 s > 100 Hz, 3 s < 10 Hz

Ambient temperature

0...+60 0C

0...+60 0C 0...+60 0C 0...+50 0C -10...+50 0C

Case dimensions

22.5 x 82 x 99 mm

22.5 x 60 x 75 mm 9 x 81 x 58 mm 22.5 x 82 x 99 mm 125 x 125 x 75 mm

Mounting

DIN-rail, DIN46277

DIN-rail, DIN46277 DIN-rail, DIN46277 DIN-rail, DIN46277 Wall mounting

Terminal blocks

2.5 mm2

2.5 mm2 2.5 mm2 2.5 mm2 2.5 mm2

Notes

output load max. 1,000 W when active output connection

input loop voltage drop 5V + output, e.g. output load 200W

(100W = 2V),

Uin = 5V+4V

Very narrow size reduces installing space.

Max. output load depends on power supply used.

Pulse converter with galvanic isolation and 24 VDC supply voltage.

Unit provides 12 VDC supply for sensor.