Isolators / Converters |
|
Type |
H641 |
H6570 | H6580 | H6410 | H6400 |
|
Input |
0/4...20mA, 20...4mA, 0...5/10V, 10...0V, -10...+10V, 2-wire 4...20mA, potentiometer, mV-input |
4...20mA loop powered isolator but also converter | 4...20mA, 0...10V | max. 5kHz, min. 0...5V, max. 0...24V, Namur, NPN-/PNP-sensor, closing contact, pick-up | max. 5kHz, min. 0...5V, max. 0...24V, Namur, NPN-/PNP-sensor, closing contact |
|
Output |
0/4...20mA, 20...4/0mA reversed, 0...5/10V, 10...0V reversed, -10...+10V, 2-wire 4...20mA passive output |
0...20mA, 4...20mA, 0...10V, loop powered converter | 4...20mA 2-wire connection | 0/4...20mA | 0/4...20mA selectable pulse divider 1...4096 via DIP-switches closing or opening contact |
|
Selection |
DIP-switches & jumpers |
Factory selected | Factory selected | By DIP-switches | Range resistors |
|
Galvanic isolation |
1,000V |
2,000V | Optical, 1,000 VDC | ||
|
Power supply |
22...30 VDC |
Loop powered | 2-wire transmitter, 12...36 VDC | 22...30 VDC | 230, 115 VAC, 24 VDC/AC |
|
Effect demand |
40 mA V-output, 60 mA I-mA output, 80 mA 2-wire output |
Input voltage drop example below | 60 mA | 2 VA | |
|
Accuracy |
< 0.05 % of span |
< 0.05 % of span | 0.05 % of span | 0.3 % of span | 0.2 % of span |
|
Typical linearity |
< 0.05 % of span |
< 0.03 % of span | 0.05 % of span | ||
|
Input resistance |
50 W for current, > 100 MW for voltage |
50 W for current | |||
|
Output load |
max. 500 W |
max. 300 W | 2-wire output | max. 500 W | 500 W |
|
Response time |
Selectable damping 10, 250, 500, 700 ms |
100 ms | 100 ms | 3 s (output 63 %) | 1 s > 100 Hz, 3 s < 10 Hz |
|
Ambient temperature |
0...+60 0C |
0...+60 0C | 0...+60 0C | 0...+50 0C | -10...+50 0C |
|
Case dimensions |
22.5 x 82 x 99 mm |
22.5 x 60 x 75 mm | 9 x 81 x 58 mm | 22.5 x 82 x 99 mm | 125 x 125 x 75 mm |
|
Mounting |
DIN-rail, DIN46277 |
DIN-rail, DIN46277 | DIN-rail, DIN46277 | DIN-rail, DIN46277 | Wall mounting |
|
Terminal blocks |
2.5 mm2 |
2.5 mm2 | 2.5 mm2 | 2.5 mm2 | 2.5 mm2 |
|
Notes |
output load max. 1,000 W when active output connection |
input loop voltage drop 5V + output, e.g. output load 200W (100W = 2V), Uin = 5V+4V |
Very narrow size reduces installing space. Max. output load depends on power supply used. |
Pulse converter with galvanic isolation and 24 VDC supply voltage. |
Unit provides 12 VDC supply for sensor. |